The following table are specifications for the 39M2816 DPI C13 PDU+.
Specifications Line cord PN Line cord PN Line cord PN Line cord PN Line cord PN
Input Line
40K9611
Cord Type*
Type
32A/380-
415V
Phase
Three
Outlets types
twelve IEC
C13
Power
22080VA @
Capacity**
230V
Power Limit
10A
per Outlet
Grouping
Two C13
outlets per
breaker /
Four C13
outlets per
phase
Power Limit
20A per
per Group
breaker 32A
per phase
Power Limit
96A
per PDU
Monitoring/
Yes/No
Switching
(Monitoring only)
U Space
1U or side pocket
Grounding
Yes on back panel
Screw
* For input line cord part numbers refer to the
** For the purpose of this table, you can consider 1 VA = 1 Watt.
109
40K9612
40K9613
32A / 220-
63A/220V-
240V
240V
Single
Single
twelve IEC
twelve IEC
C13
C13
7360VA @
14490VA @
230V
230V
10A
10A
Two C13
Two C13
outlets per
outlets per
breaker
breaker
20A per
20A per
breaker
breaker
32A
63A
Input Line Cords
40K9617
40K9618
32A / 230V
30A / 230V
Single
Single
twelve IEC
twelve IEC
C13
C13
7360VA @
6900VA @
230V
230V
10A
10A
Two C13
Two C13
outlets per
outlets per
breaker
breaker
20A per
20A per
breaker
breaker
32A
30A
section.